SMS Commands for TrackSo Data Logger

You are here:
← All Topics

Following is the list of commands which can be used on TrackSo Data Loggers:

Applicable Model No.Purpose of CommandSMS CommandSample Response
WT-805M, WT-800, WT400M, WT410 M, WT420 M

For Checking Logger Status



Provides
IMEI
DTM
Network Name
GPRS Status
No. of Logs
*2222#<Stat.gsm>WT GW-MODBUS
IMEI=867481034271712
DTM=28-09-2018 07:55:15
NW=Idea Cellular Ltd-H
SIG=24
GPRS=1:CONT
PIP=H:CONT
NTP=1
Log=8148
WT-805M, WT-800, WT400M, WT410 M, WT420 MRestart Logger*2222#<Cmd.sysrst: >WT XXX YYY
Device goingto Restart;
WT-805M, WT-800, WT400M, WT410 M, WT420 MTo check Slave Status*2222#<Dbug.mbcom: >

Modbus Status
1 4 0 X 10 65
2 4 0 X 10 65
1,2= Modbus Slave Id
X = Device status
– 0 : Live
– 1-20 : Standard Modbus Error
– 21: No Reply from Slave (Connection/setting error)

Full Error List available here

WT GW-MODBUS

Cmd Max=3
Slave Max=2
BOVF=0
SlvId TxCnt ErrCnt Stat Tms DCnt
--------------------
1 4 0 0 10 65
1 4 0 0 10 199
2 4 0 0 10 41
WT-805M, WT400M, WT410 M, WT420 MSchedule Modbus
Data Polling
for specific time

*2222#<Cfg.cont: SCH-POLL=”p,aa:bb,xyz” >


where
p– 1 or 0 ( 1 -Activate , 0- Deactivate)
aa:bb– Start time in UTC (ex- 00:00 hrs (UTC) = 5.30 AM (IST))
xyz- No. of minutes for polling data (ex- 860)

Sample-*2222#<Cfg.cont: SCH-POLL=”1,00:00,860″ >
Configuration Set Ok;
WT-805M, WT-800, WT400M, WT410 M, WT420 MEnable Power
Fail/Restore SMS Alerts
A mix of Two SMS

*2222#<Cfg.device: NAME=”Building 1”,PH1=”8800xxx765″,PH2=””,PH3=”” >

*2222#<Cfg.alert: AEN=”3″,PWR=”1″,SHT=”0″,INP=”0″,OUT=”0″ >


Detailed usage guide available here

Configuration Set Ok;
WT-805M, WT400M, WT410 M, WT420 MModbus Write Command
via SMS
*2222#<DEVCMD: MBCMD=XXXXXXXXXXXX0000 >

where XXXXXXXXXXXXXXXX is Modbus command
which you wish to send with CRC modified to 0000
Note: SMS command is case sensitive

Detailed usage guide available here

Reply 1:
WT GW-MODBUS



REPLY 2:
XXXXXXXXXXXX5D31
(with correct CRC calculated)

WT-805M, WT400M, WT410 M, WT420 MIdentify Network and
Device Status in single SMS
*2222#<status>

Response explanation:

IMEI,Network Status,GPRS Status
APN
Modbus Status
1 X
2 X
1,2= Modbus Slave Id
X= Device status
– 0 : Live
– 1-20 : Standard Modbus Error
– 21: No Reply from Slave (Connection/setting error)

Full Error List available here

WT DSouth
866600042829549
Vodafone – Raja-R
GPRS=1:CONT H:CONT
apn
WT-805M-8
1 0
1 0
2 0
3 0
3 0
5 0

WT-805M, WT400M, WT410 M, WT420 MRestart Logger*2222#<restart>WT XXX YYY
Device goingto Restart;