Basic difference between Modbus RTU RS485 and Modbus TCP/IP for Solar Power Plants Applications

You are here:
← All Topics

Modbus RS-485 & Modbus TCP/IP interfaces are widely used in the industry for connecting & monitoring various equipment.

Modbus RTU RS485: Remote Terminal Unit (RTU) Modbus over a serial RS485 connection
Modbus TCP: Modbus over an Ethernet connection

The following table covers the basic differences with respect to its applications in Solar Equipments.

Modbus RTU RS485

Modbus TCP/IP

RTU is in existence for long around, and it is supported by lots of Inverter , meter & sensor manufacturers Modbus TCP/IP is easy to integrate & can be used with existing Ethernet network equipments (Intranet or Internet), which are inexpensive and widely available.
Max no. of 32 devices in one segment Upto 256
The maximum distance of RS-485 without using a repeater is 1.2km at baud rates up to 90Kbps. Depends on capacity of communication cable (Ex- 100m with Cat6).
It can use existing intranet/internet network.
Can reach 10 Mbit/s at 10m.
(Speed of operation depends on length of the line )
Modbus/TCP will be sent at speed of your Ethernet connection
(Most Modbus/TCP hardware these days is 10 or 100 Mbit/s)

Some Frequently Asked Questions

How many slaves can be connected for other protocols such as RS232 ?
  • RS-232 only allows for one slave.
  • RS-422 can address up to 10 slaves.
  • RS-485 can address up to 32 slaves.
Can i monitor more than 32 slaves on Rs485

Our Modbus RTU supports the node range from 0-255. After 32 nodes (1 master + 31 slaves), you may need RS-485 repeaters to ensure proper communications. This depends on a number of different items, including if the RS485 transceivers are full or quarter load.

Reference- https://community.exchange.se.com/t5/Building-Automation-Knowledge/What-is-the-maximum-number-of-nodes-and-points-allowed-while/ta-p/8486

Can i extend RS-485 network beyond 1.2KM?

RS-485 network distance can be extend by adding RS-485 repeater or optically Isolated Repeater every 1.2KM

References

1) Modbus Messaging on TCP/IP Implementation Guide V1.0b (PDF), Modbus Organization, Inc., October 24, 2006, retrieved 2017-01-07

2) “Modbus Application Protocol V1.1b3” (PDF). Modbus. Modbus Organization, Inc. Retrieved 2 August 2013.

3) Free Modbus Guide for Field Technician